This software applies to the following DEIF products:

Du er ved at downloade 6.04.3

The main changes implemented since the last version are as follows:

PM compatibility: 1.24.1

Corrections:

  • Simulating grid frequency via multi-input for droop curve 1 was off by a factor of 10.
  • A change to a different configuration than application 1 using the USW would not persist past a powercycle of the controller.
Ver. Dato Description

6.04.3

16-11-2021

PM compatibility: 1.24.1

Corrections:

  • Simulating grid frequency via multi-input for droop curve 1 was off by a factor of 10.
  • A change to a different configuration than application 1 using the USW would not persist past a powercycle of the controller.

6.04.2

10-11-2021

PM compatibility: 1.24.1

Corrections:

  • Minimum load was not respected when using droop curve 1.

6.04.1

22-10-2021

Not UL approved version

PM compatibility: 1.24.1

Corrections:

  • Island ramping when loadsharing over CAN or analogue line now works again.
  • Fixed an issue with the EEPROM storage layout.
  • Changing application configuration with jump menu #9160 would not be stored in longterm storage.
  • If the ground relay was enabled and the application configuration was a non PMS single DG, the GB would not open when deloaded.

6.04.0

07-10-2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • New EIC measurement area included with data validation.
  • Support new J1939 priority for exhaust temperatures (CAT).
  • Extended #1230 G f> 3 and #1260 G f< 3 timers to 2000.0 [s].
  • Power ramps improved. 6- Feedforward control to suppress frequency and voltage disturbances in fixed power, reactive power control (in LFSM situations).

Changes:

  • S nominal import/export set points are obsolete. Both are replaced by one S nominal per measurement area.
  • Maximum timer extended to 3200.0 s on a number of protections (AC, digital inputs, MPU, EIC).

Corrections:

  • Translation now works even though no DU-2 is mounted AND only new language is written.
  • Deload TB before GB opens function works correctly in PEAK SHAVING.
  • PMS priority change via M-Logic or Modbus now works correctly.
  • df/dt now operates on the mains side measurements.

6.03.1

13-09-2021

Not UL approved version

PM compatibility: 1.24.1


Corrections:

  • Freeze regulation during FRT now working correctly.

6.03.0

15-07-2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • Two new General Purpose PID´s (GP-PID) 5 and 6 are added. Also added new parameters for all GPIDs (1 to 6) to configure the regulator set point.
  • Support of 3 x 2 A/Os on IOM 220/IOM 230 for GP-PID 1 to 6 is added.
  • Support for John Deere Stage V EIC protocol is added.

Changes:

  • TCP/IP security update.

Corrections:

  • Limit events are added in M-Logic for Extended M-Logic Alarms.
  • "Fuel optimization" and "Fuel optimization + running hours" is now working when using percent values.
  • TDU is now able to change to BLOCK mode (requires TDU version 1.3.7.0).
  • Short circuit supervision (option T1) now includes PV and battery units connected (requires ASC-4 version 4.17.0).
  • EIC transmission rate stability is improved.
  • Default IP address is changed from 192.168.2.2 to 192.168.2.21 to match the TDU default address.

6.02.1

06-05-2021

UL approved version

PM compatibility: 1.23.0

Corrections:

  • Plant management Group Tie redundancy is improved in AUTO and ISLAND plants to secure groups without a start signal to start and stop properly when in need of a redundant unit.
  • Corrected the text for IP, subnet, gateway.
  • Corrected that alarm and battery logs where not shown correctly when the number of entries reached maximum.

6.02.0

06-04-2021

Not UL approved version

PM compatibility: 1.23.0

New features:

  • Support for FPT + Iveco Stage V EIC protocol is added.
  • Four new M-Logic alarms with extended delay are added in menu 3620-3650.
  • VDE 4110 support with MAINS unit in power management is added.
  • Event log entry is added when application setup changes.
  • Support of DVC 550 PSS is added.
  • New GOV and AVR step test are added in parameter group #2970.

Changes:

  • CIO alarms are added to Modbus.
  • Minimum set-point is lowered to 10% for low AC voltage alarms.

Corrections:

  • QSK60G EIC auto view is showing correct values.
  • DVC 550/D550 communication when EIC and Ext. Modules DEIF protocols were selected on two CAN ports is corrected.

6.01.2

15-03-2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • The 4-20 mA output of the option EF5 analogue card now works again.
  • Power factor set point on Modbus is now correctly initialized after a power-up.

6.01.1

12-02-2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • Corrected an issue that caused a mains controller to not be able control the PF setpoint (superior cos phi) on genset controllers.
  • N+X now works when Fuel optimisation is in use.
  • Priority update now works when more than 16 gensets or more than 16 mains are present in a plant configuration.
  • PMS priority data is correct maintained internally in all genset controllers.
  • Breaker feedbacks are properly updated on the I/O status and the I/O setup page.

6.01.0

11-01-2021

UL approved version

PM compatibility: 1.22.0

New features:

  •    Added support for Yuchai Diesel+Gas J1939 protocols.
  •    Addded support for Weichai Diesel+Gas J1939 protocols.
  •    Added support for MAN J1939 protocol.

6-00-0

07-01-2021

Not UL approved version

PM compatibility: 1.22.0

   - Initial release.