Select your business area

We use this information to provide content associated with segment of your choice.
You can change your selection any time.
This governor and AVR module has four relay outputs, two analogue outputs and a pulse width modulation output, and two analogue inputs. These I/Os are configurable. GAM3.1 also has terminals for analogue load sharing (future use).

Physical connections

  • 1x Relay output - configurable
    • 30 V DC, and 6 A
  • 1 x Active power (P) (kW) load sharing (future use)
    • -5 to 5 V DC
  • 1 x Reactive power (Q) (kVAR) load sharing (future use) 
    • -5 to 5 V DC
  • 2 x Analogue current or voltage output (analogue current or voltage output) – Active outputs
    • -20 to 20 mA, or 0 to 20 mA, or 4 to 20 mA, or any custom range between -25 and 25 mA
    • Voltage output (DC)-10 to 10 V, 0 to 10 V, 0 to 5 V, -5 to 5 V, 0 to 3 V, -3 to 3 V, or 0 to 1 V, or any custom range between -10 and 10 V
  • 1 x Pulse width modulation (PWM) output
    • 500 Hz ±50 Hz
    • Voltage: Low level: < 0.5 V. High level: > 5.5 V. Maximum: 6.85 V.
  • 2 x Analogue current or voltage input configurable (galvanically connected)
    • From active transmitter: 0 to 20 mA, 4 to 20 mA, or any custom range between 0 and 24 mA
    • Voltage inputs (DC) -10 to 10 V, 0 to 10 V, or any custom range between -10 and 10 V