Grid Protection Module GPM5∙1

Direct 690 V 3-phase voltage, current and power measurement (class 0.5)
The GPM5∙1 module is a class 0.5 grid measurements and protection module, fully configurable from the main application. The module has an onboard processor for sampling of grid measurements such as three-phase voltages, currents, phase angles and power vector measurements. The availability of these measurements/calculations as variables takes load from the application, thus making it faster. The GPM5∙1 module enables the application to read the following values directly from the process image, thus reducing the processing time of the application.
A special feature of the GPM5∙1 card is that it has a true class 0.5 calculation, also on power measurements. The module features class 0.5 measurements of voltage, frequency, current, power, reactive power and phase angle
Inputs
- 2 x direct three phase voltage inputs (L1, L2, L3, N)
- Input range: 0 to 690 V
- Measure range: 40 to 690 V
- Frequency: 40 to 70 Hz
- Load max.: 0.5 mA or 0.3 VA per phase
- Overload: 130 % continuously, 200 % for 10 s
- External fuse, maximum 2 A slow-blow
- UL/cUL: Maximum 600 V L-L, above 2000 m altitude maximum 520 V
- 1 x direct three phase current input (L1, L2, L3)
- Input range: 0 to 1 or 0 to 5 A
- Frequency: 40 to 70 Hz
- Load max.: 0.4 VA per phase
- Overload: 20 A for 60 s, < 75 A for 10 s, < 300 A for 1 s
- UL/cUL: From listed or R/C (XODW2.8) current transformers
Outputs
- 2 x digital relay outputs (normally open) with feedback supervision
- 24 V, maximum 1 A resistive
Certification class
- 0.5 measurement of voltage, frequency, current, power, reactive power, phase angle.
Galvanic separation
- 3.25 kV 50 Hz isolation between voltage measurement inputs individually and between voltage measurement inputs and all other potentials.
- 550 V 50 Hz isolation between relay outputs, digital inputs (feedback supervision) and all other potentials.
Safety
- Installation (over-voltage) category III, 600 V, pollution degree 2.
- EN 61010-1 tested at 50 Hz, 60 s.
- Each galvanic group tested to other galvanic groups and to Protective Earth, PE.
Accuracy
- 0.5 % at reference temperatures
- 1.0 % at operational temperatures
- IEC 60688
Size
- 6 TE (30.48 mm)
Power consumption
- Maximum 4 W